The Thermal Transfer UC/UCV Series features all-steel construction with a U-tube design that reduces stresses caused by thermal expansion. The UCV features rotated shell ports for removal of condensate. The tube bundle, removable for servicing or replacement, is standard on all models. This series heat exchanger is ideal for steam and large temperature differential applications.
This heat exchanger can be used as a water heater using steam or as a condenser for your very specific application.
Material configurations can be steel or stainless steel with copper tubes
Features
Steam & large temperature differentials
“U” tube
Removable tube bundle for servicing
3/8″ Tubes
Built-in expansion chamber
Threaded or flanged connections
Mounting brackets included
Steel shell assembly
Reduces thermal expansion stresses
Product Options
Wide variety of materials available
Custom sizes/designs
Stainless steel hardware and mounting
Ratings
UC Series:
Maximum Operating Pressure – Shell Side 250 PSI
Maximum Operating Pressure – Tube Side 150 PSI
Maximum Operating Temperature 400°F
UCV Series:
Maximum Operating Pressure – Shell Side UCV-600, 800 and 1000 250 PSI
Maximum Operating Pressure – Shell Side UCV-1200 and 1700 150 PSI
Maximum Operating Pressure – Tube Side 150 PSI
Maximum Operating Temperature 400°F
Materials
UC/UCV Series:
Tubes – Copper
Tube Sheets – Steel
Shell – Steel/316L stainless steel (UCV)
Shell Connections – Steel
Baff les – Stainless steel
End Bonnets – Cast iron
Mounting Brackets – Steel
Gaskets – Non-asbestos fiber/nitrile rubber
Nameplate – Aluminum foil
Contact your local Thermal Products office at 518-877-0231 or sales@thermalproducts.com