Description

Indeeco cooling tower heater panels are installed in thousands of cooling towers across North America and are widely recognized for their quality, reliability, and ease of installation. In addition to standard offerings, Indeeco manufactures custom cooling tower heaters and control panels for many leading cooling tower manufacturers, including Baltimore Aircoil (BAC), Marley, SPX Cooling Technologies, EVAPCO, Delta Cooling Towers, and others. These systems are specifically designed for cooling towers with water basins to provide dependable freeze protection in demanding operating environments.

Standard Features

  • Epoxy seals offer a moisture resistant seal where fluid temperatures do not exceed 250° F
  • All units are UL/CSA listed
  • CSA listed heaters for Class 1, Division 1 and 2, Groups B, C, D are available, consult factory
  • Standard nested third element, the 360° repressing and a solid element spacer to prevent hot spots
  • All fittings are single piece forgings either brass or 304 stainless steel
  • Convenient lead wire power connections
  • All heaters are hydro-tested at 240 PSI
  • NEMA 4X cast aluminum terminal boxes are attached via a NPT threaded connection to the top of the fitting
  • Terminal boxes include ground lugs and are removable, adjustable and replaceable
  • All Indeeco immersion heaters are manufactured in the United States

Cooling Tower Panels

Indeeco Cooling Tower Control Panels provide a streamlined, cost-effective solution by consolidating temperature and water level controls into a single, pre-engineered, factory-assembled control package. By replacing multiple individually mounted devices, these panels simplify installation, reduce field labor, and improve overall system reliability.

Engineered with high-quality components for dependable performance, Indeeco control panels help maintain optimal cooling tower operation while minimizing system complexity. Indeeco also manufactures cooling tower heaters and control panels for many leading cooling tower manufacturers, including Baltimore Aircoil (BAC), Marley, SPX Cooling Technologies, EVAPCO, Delta Cooling Towers, and others, for cooling towers with water basins requiring reliable freeze protection and control.

Panel Performance Features:

Ambient Temperature Range
-10° F to 104° F

Fail Safe
Fail Safe Output relay is de-energized if the input sensor is either open or short-circuited preventing heater burnout problems.

NEMA 4X Enclosure
Includes pre-mounted electrical hubs for conduit connections.

Single Probe with Dual Sensing
Senses both water temperature and water level. Sensor probe supplied with 12 ft outdoor rated cord pre-wired to control board. Probe also supplied with PVC hub connector for attachment through cooling tower basin wall

Probe Construction
Constructed out of 316 SST tubing and 304 SST fitting to minimize corrosion. Probe can be installed horizontally or vertically with a pressure rating of 15 psi.

Remote Interlock Terminal Block
A means of safeguarding to prevent operation if an interlock is open.

Lower Cost
Installation time and cost are reduced by replacing individually mounted temperature and liquid level control devices with one pre-engineered and assembled control package that requires only one probe to sense both water temperature and level.

Standard Options
Door disconnect, fusing, circuit breaker, fusing with door disconnect, and circuit breaker with door disconnect. Direct immersion cords, custom cord lengths up to 125 ft, 0° F – 100° F adjustable control board, 304 SST enclosure.

New Optional Features:

Digital Temperature Display
The digital temperature display provides more precise and reliable temperature readings, enabling better control and optimization of the cooling process. This leads to improved energy efficiency, enhanced performance, and better overall system health.

Adjustable Setpoint
An adjustable temperature setpoint on a cooling tower basin offers several benefits, including energy savings, optimized system performance, and enhanced control over water temperature. This allows for fine-tuning the cooling tower’s operation based on changing needs and conditions, leading to improved efficiency and reduced operating costs.

Optional RS485 Communication
RS485 communication allows operators to monitor the cooling tower’s water basin, including temperature and conductivity. Operators can remotely control the cooling tower’s basin heater operation, such as adjusting setpoints.

Enclosure Heater
An integrated enclosure heater is provided to ensure reliable operation at low ambient temperatures as well as prevent issues related to condensation inside the enclosure.

Low Temp Alarm
An optional set of contacts provides remote indication of low basin temperature.

Low Water Alarm
An optional set of contacts provides remote indication of low basin water level.